Table of contents
Pre-Checks
- Check that the 1pps is connected to all R2DBE units (frontside)
- Check that the IFs are connected to the Block Down Converter (BDC) with RCP and LCP as labeled on the backside
- Check that the 10MHz signal is connected to the clock synthesizer unit
- Check that the 10MHz signal is connected to the BDC unit
- Check that the both IF input pins of all R2DBE units (frontside) are connected by cable
- Check that all R2DBE units are connected by ethernet (PPC net port) to the network hub box (backside)
- Check that the noise generator unit is connected by ethernet to the network hub box (backside)
- Check that all mark6 units are connected by ethernet cable to the the network hub box (backside)
- In case you want to inspect the R2DBEs autocorrelation spectra make sure you insert a tone into the noise generator unit (backside)
Startup sequence
- power on the mark6 units
- power on the clock synthesizer units
- power on the BDCs
- power on the R2DBEs
- power on the noise generator (optional)
Verify startup
- log into pv-mark-1 as user oper. If logging-in does not work the mark6 machine is probably stuck in booting. Connect a display and keyboard and check.
ssh pv-mark6-1 -l oper -X
- do the same for the other recorders
- log into the control computer as user oper. Verify that all the R2DBEs units have booted up by trying an ssh connection:
ssh r2dbe1 -l root ssh r2dbe2 -l root ... exit from r2dbe1, r2dbe2, ...
if one of the units does not boot consult the Troubleshooting section below.
Configuring the R2DBEs
- log-into the control computer as user oper
- initialize all the R2DBE units by running:
start_backend.py /home/oper/pv-backends.conf
- alternatively the backends can be initialized individually:
start_backend.py /home/oper/r2dbe1.conf start_backend.py /home/oper/r2dbe2.conf ... start_backend.py /home/oper/r2dbe4.conf
Troubleshooting
R2DBE unit does not boot
- Connect a USB cable from the R2DBE (backside "FTDI USB" port) to one of the USB ports on pv-mark6-1
- log-into pv-mark6-1 as root
- run:
screen /dev/ttyUSB2 115200
- hit the "enter" key. If the log-in prompt of the r2dbe unit appears go on to section XXXX
- reset the R2DBE unit. In the screen window you should see the R2DBE booting. Inspect any messages that could indicate an error
- press ctrl-a to leave the screen session
R2DBE unit has booted but is not reachable from the mark6 machines
- very likely the R2DBE has been assigned the wrong IP-adress by the dnsmasq service running on pv-mark6-1
- log-into pv-mark6-1 as user root
- run
/etc/init.d/dnsmasq restart
- reset the R2DBE unit